E6581611
F-116
6
6.31 Override
f205 : VIA input point 1 rate
f206 : VIA input point 2 rate
f214 : VIB input point 1 rate
f215 : VIB input point 2 rate
f220 : VIC input point 1 rate
f221 : VIC input point 2 rate
f660 : Override addition input selection
f661 : Override multiplication input selection
f729 : Operation panel override multiplication gain
• Function
These parameters are used to adjust reference frequencies by means of external input.
[Parameter setting]
Title Function Adjustment range Default setting

VIA input point 1 rate 0-250 (%) 0

VIA input point 2 rate 0-250 (%) 100

VIB input point 1 rate -250-+250 (%) 0

VIB input point 2 rate -250-+250 (%) 100

VIC input point 1 rate 0-250 (%) 0

VIC input point 2 rate 0-250 (%) 100
f660 Override addition input selection
0: Disabled
1: Terminal VIA
2: Terminal VIB
3: Terminal VIC
4:
fc
0
f661
Override multiplication input
selection
0: Disabled
1: Terminal VIA
2: Terminal VIB
3: Terminal VIC
4:
f729
0

Operation panel override
multiplication gain
-100-+100 (%) 0