E6581611 
 
F-34 
6 
  Setting of switching terminals 
To switch to motor 2, assign the following functions to a terminal not being used. It is also possible to switch 
to acceleration/deceleration 2 (AD2). Refer to section 6.27 for details.  
It is possible to set 3 functions for terminal F and R, and 2 functions for terminal S1 and RES. 
 
Input terminal function number 
Parameters changed from applicable parameters and 
default standards
24 
AD2 
26 
AD3 
28 
VF2 
32 
OCS2
152 
MOT2 
OFF  OFF OFF OFF OFF 
Default setting :  pt, vl, vlv, vb, 
thr, acc, dec, 
fs02, f601 
ON  OFF OFF OFF OFF 
acc→fs00, dec→f501, f502→fs03 
OFF ON OFF OFF OFF 
acc→fs10, dec→f511, f502→fs12
OFF OFF ON OFF OFF 
During stop : pt→V/F constant, vl→f170,  
vlv→f171, vb→f172, thr→f173 
During run : vl→f170, vlv→f171,  
vb→f172 
OFF OFF OFF ON OFF 
f601 → f185 
-  OFF - - ON 
→, →, → , →, 
→( is fixed when =or), 
→,→, →,
→ 
Note 1: Each of the following numbers (25, 27, 29, 33, 153) are reverse signals.  
Note 2: pt and "V/F constant" cannot be switched while running. Stop the motor before switching.  
  It is necessary to wait to start the motor for 0.2 seconds or more after switching it. 
  vl and f170, vlv and f171, vb and f172 can be switched while running. 
Note 3: If motor is switched, the setting to retain and subtract an integral value of motor electronic thermal is possible. 
Refer to section 5.6 for details. 
 
 
  Example of setting a terminal for switching: Sink logic 
 
F (F: Forward run) 
CC
S2(VF2) 
S3(OCS2) 
S1(AD2) 
Forward run command
2nd acceleration/deceleration switch
2nd stall prevention operation switch 
2nd V/F setting switch 