  The jog run setting terminal (RES-CC) is enabled when the value of operation frequency is that of the jog 
run frequency and below.  
This connection does not function when operation frequency exceeds the jog run frequency. 
  The motor can be operated in jog mode while the jog run setting terminals are connected (RES-CC). 
  Jog run has priority to new operation command given during operation. 
 Even for f261 = 0 or 1, an emergency DC braking (f603 = 2) is prior to the setting. 
  No limits are imposed to the jog run frequency by the upper-limit frequency (parameter ul). 
 
  Panel jog mode (if f262 is set to 1) 
  The direction of rotation can change by using extension panel. 
    Using RKP007Z : Display switches to fjog and rjog by every pressing the FWD/REV key. 
  Using RKP002Z : Pressing the UP key changes display to fjog and pressing the DOWN key  
  changes display to rjog. 
 When fjog is displayed, the inverter will be placed in forward jog run mode as long as the         
key is pressed. 
 When rjog is displayed, the inverter will be placed in reverse jog run mode as long as the         
key is pressed. 
  If you press and hold down the           key for 20 seconds or more, the key failure alarm “e-17” will 
be displayed. 
 
Here is the sequence in which modes change each time you press the               key. 
 
 
 
Standard monitor 
mode 
Status monitor 
mode 
Setting monitor 
mode 
Pan el jo g mod e 
MODE 
MOD E
 
MOD E
 
MODE
 
 
Note: When the inverter is in operation (RUN lamp is blinking) or when an operation command is issued  
(RUN lamp is lighting), the inverter cannot be switched to panel jog mode. 
RUN 
RUN
MODE
 
 
ST-CC 
 
F-CC 
 
R-CC 
  RES-
Frequency command input
 
Reverse
Forward
Forward
 
Set frequency 
  (=18) 
Forward