11.3 Extended parameters 
 
 Input/output parameters 1 
Title 
Communication 
No. 
Function Unit
Minimum 
setting unit 
Panel/Commun
ication 
Adjustment range 
Default 
setting
User 
setting 
Reference 
 
0100 Low-speed signal 
output frequency 
Hz 0.1/0.01 0.0- 0.0  6.5.1 
 
0101 Speed reach  
setting frequency 
Hz 0.1/0.01 0.0- 0.0  6.5.3 
 
0102 Speed reach  
detection band 
Hz 0.1/0.01 0.0- 2.5  6.5.2 
6.5.3 
 
0104 Always active 
function selection 1
-  - 
0-7, 10-153: *6 
8,9: - 
0 (No 
function)
 6.7.1 
 
0105 Priority selection 
(Both F and R are 
ON) 
-  - 
0: Reverse 
1: Deceleration Stop 
1  6.6.1 
0107 Analog input 
terminal selection 
(VIB)
 
-  - 
0: 0-+10V 
1: -10-+10V
 
0  6.6.2 
6.10.2 
7.3 
 
0108 Always active 
function selection 2
- 
- 
0-7, 10-153: *6 
8,9: - 
0 (No 
function)
 6.7.1 
0109 Analog/logic input
selection  
(VIA/VIB) 
- - 
0: VIA - analog input 
VIB - analog input 
0  6.6.3 
6.7.2 
6.10.2 
7.2.1 
7.3 
1: VIA - analog input 
VIB - contact input  
2: - 
3: VIA - contact input (Sink) 
VIB - contact input  
4: VIA - contact input (Source) 
VIB - contact input  
 
0110 Always active 
function selection 3
- - 0-7, 10-153: *6 
8,9: - 
6 
(ST) 
 6.7.1 
 
0111 Input terminal 
selection 1A (F) 
- - 0-203  *6  2 
(F) 
 6.7.2 
7.2.1 
 
 
0112 Input terminal 
selection 2A (R) 
- -  4 
(R) 
 
 
0113 Input terminal 
selection 3A (RES)
- -  8 
(RES) 
 
 
0114 Input terminal 
selection 4A (S1) 
- -  10 
(SS1) 
 
 
0115 Input terminal 
selection 5 (S2) 
- -  12 
(SS2) 
 
 
0116 Input terminal 
selection 6 (S3) 
- -  14 
(SS3) 
 
 
0117 Input terminal 
selection 7 (VIB) 
- -  16 
(SS4) 
 
 
0118 Input terminal 
selection 8 (VIA) 
-  -  8-55  *6  24 
(AD2) 
 
*6: Refer to section 11.6 for details about input terminal function. 