EasyManua.ls Logo

TOTALINE CPE230RF - Page 8

TOTALINE CPE230RF
16 pages
Print Icon
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
Occupied 2, Occupied 3, Unoccupied) time periods. Each occupied time pe-
riod has a start time, stop time, heating set point, and cooling set point. The
unoccupied time period has a heating set point and a cooling set point.
The unoccupied time period is active whenever an occupied time period is
not active. Fill in Table 1 on page 12 as an aid to programming the daily
schedules.
PROGRAMMING MODE To program the daily schedules, perform the
following procedure:
1. Enter programming mode by pressing the Mode and UP ARROW but-
tons at the same time. The Occupied 1 annunciator will appear on the
thermostat display. See Fig. 5. Use the UP ARROW and DOWN AR-
ROW buttons to set the maximum number of Occupied periods avail-
able. The thermostat can be set to 1, 2, or 3. After the number of Oc-
cupied periods has been selected, press the Mode button.
2. The cooling set point for Occupied 1 will be displayed. Use the UPAR-
ROW and DOWN ARROW buttons to raise or lower the cooling set
point until the desired temperature is shown. The range of acceptable
values is 35 to 99 F (1 to 37 C). Press the Mode button to continue. See
Fig. 4.
Fig. 4 Setting Occupied 1 Set Points
8

Related product manuals