SETTINGS – TIME BETWEEN FUEL TYPES
22
DEFINITION DEPENDENCIES FUNCTION
Pressing the Time Between Fuel Types field in the
“System Settings Screen” will invoke the “Time
Between Fuel Types Screen” which will allow a time
choice from 10 minutes to 25 minutes for the time
between fuel choices functionality, adjustable in 5
minute increments.
If there are not
multiple fuel types,
this logic will not be
used.
This functionality is used to set the
minimum time limit between switching from
one fuel type to another (other staging rules
may also be in effect).