Page 16.3
Dry Contact ProgrammingDry Contact Programming
OCCUPIED 1 OR SERVICE THE CONDENSATE DRAIN PAN - If 
     Occupied 1 is selected in step #41 (below), when the dry contact is 
     energized the thermostat will be forced into Occupied 1 setpoints
     and the Occupied 1 icon will blink (Section 6).  
     If Service Pan is selected, when the dry contact is energized the 
     thermostat will lockout Y1 (compressor) and write Service Pan on 
     the display.
Press the PROGRAM button to leave the Setup screens. If no buttons are 
pressed, the display will leave the setup screens after 30 seconds.
PROGRAM
Press
Select Occupied 1 to enable 
Occupied 1 setpoints when 
the dry contact is energized.
Select Service Pan to lockout 
Y1 when the dry contact is 
energized.
Service Pan
Occupied 1
Setup
4 i
occupied
1
Connect wires to a time 
clock or other device to 
force the thermostat into 
Occupied 1.
Y1
G
R
C
MISC2
CK1
CKGND
W1/O/B
MISC1
RS+5
RS1
RSGND
W2
RS2
MISC3
Y1
G
R
C
MISC2
CK1
CKGND
W1/O/B
MISC1
RS+5
RS1
RSGND
W2
RS2
MISC3
Connect wires to a device 
that will energize when 
the Condensate Drain 
Pan is full.
OR
Occupied 1 Service Pan
PROGRAM
MODE
MODE
Press the MODE button.  While holding 
the MODE, press the PROGRAM 
button to enter Setup screens.
Press the MODE button repeatedly 
until this setup screen appears.
Note: Press the MODE 
button momentarily 
to move through the 
setup screens.  Press 
and hold the MODE 
button to move back- 
wards through the 
setup screens.
TOTALINE
16