General information
TR-Electronic GmbH 2008, All Rights Reserved Printed in the Federal Republic of Germany
Page 18 of 23 TR - EMO - TI - DGB - 0067 - 02 03/20/2020
2 General information
2.1 Description
The FB_PARAM respectively EncoTRive_Parameter_acyclic function block
enables the EncoTRive be parameterized acyclic via an S7 program. The function
block uses therefore IEC 61131 conform system function blocks for the acyclic
reading and writing of record data.
The cyclic channel is not impaired and can be used in parallel for process-oriented
parameter transfers.
With this module it is possible to write or read a drive parameter, to store the current
parameters remanently in the drive, and to restore the default factory parameters.
2.2 Sources
The example project contains all necessary modules and sources. This example
project is available on request from TR Marketing.
Two different project files are available:
- TR-EMO-SW-DGB-0028 for SIEMENS SIMATIC Manager
®
- TR-EMO-SW-DGB-0036 for SIEMENS TIA PORTAL
®
- TR-EMO-SW-GB-0038 in SCL for SIEMENS TIA PORTAL
®
2.3 Boundary conditions
The following modules are also necessary, in addition to the actual FB110 function
block (PARAM_FB):
DB110 instance data block for FB110
SFB52 (RDREC) read record from DP slave
DB112 (DB2) instance data block for SFB53 (WRREC)
SFB53 (WRREC) write record to DP slave
DB111 (DB1) instance data block for SFB52 (RDREC)
The function block has been tested using the following controls:
only TR-EMO-SW-DGB-0036:
- S7-300 (CPU 317-2PN/DP) with SIEMENS SIMATIC Manager
®
Step7 V5.2 + SP2
- S7-1500 (CPU 1511-1PN) with SIEMENS TIA PORTAL
®
V14
only TR-EMO-SW-GB-0038:
- S7-1500(CPU 1516-PN/DP) with SIEMENS TIA PORTAL
®
V16
- S7-1500 (CPU 1511-1PN) with SIEMENS TIA PORTAL
®
V16
- S7-1200 (CPU 1212-PN) with SIEMENS TIA PORTAL
®
V16
Accompanying documentation:
- encoTRive PROFINET Manual, TR-EMO-BA-DGB-0019
- Current versions, related documentation and tools: www.tr-electronic.com
2.4 Installation
The required modules specified above can be found in the example project and
copied to the target project.