EasyManuals Logo

Trane 2MCC05-C User Manual

Trane 2MCC05-C
80 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Page #36 background imageLoading...
Page #36 background image
36 MS-SVN056C-EN
Outdoor Unit Installation
Procedure for pipe connection
1. Measure the required length of tube connection and proceed as follows. First
connect the indoor unit; then connect the outdoor unit.
Fold the pipe appropriately. Do not twist the tube.
Apply refrigerant oil on the surface of the flared pipe and on the union nuts; using hands, apply
tightening torque for 3 to 4 turns, before using the wrench.
Employ two open-end wrenches simultaneously to connect or disconnect piping
Outdoor unit service valves must be totally closed (original state). In order to connect them, loosen the
nuts and connect flared tubes in a timing not to exceed 5 minutes. If nuts remain loose during extended
time, it could lead to dust and other debris entering the system and consequently causing a system
malfunction. Therefore, before the final connection, purge air from the refrigerant line.
Purge air after connecting the refrigerant line to both indoor unit and outdoor unit. Tighten nuts on the
service valves.
Fold the thin-walled connecting tube.
Cut the insulation material insulating material all over the pipe on the section to be folded.
Expose the pipe. Proceed to fold it. Once folded, cover it completely with insulating material
In order to prevent pipe from deforming or twisting, fold it at a suitable radius.
Tube
Diameter
Tightening Torque
Flare dimension (A)
(mm/inch) Flaring
Min. Max.
φ 6.4
14.2 + 17.2 N.m.
(144-176 kgf.cm)
8.3/0.3 8.3/0.3
φ 9.5
32.7 + 39.9 N.M
(333-407 kgf.cm)
12.4/0.48 12.4/0.48
φ 12.7
49.5 + 60.3 N.M
(504-616 kgf.cm)
15.4/0.6 15.8/0.6
φ 15.9
61.8 + 75.4 N.M
(630-770 kgf.cm)
18.6/0.7 19/0.74
φ 19.1
97.2 + 118.6 N.M
(990-1210 kgf.cm)
22.09/0.9 23.3/0.91
φ 22
109.5 + 133.7 N.M
(1117-1364 kgf.cm)
27/1.06 27.3/1.07
R0.4~0.8
45
°
±
2
90
°
±
4
A
Fold pipe using thumbs at a
minimum radius of 100mm/3.94in
use frozen oil
endings must
be straight

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Trane 2MCC05-C and is the answer not in the manual?

Trane 2MCC05-C Specifications

General IconGeneral
BrandTrane
Model2MCC05-C
CategoryHeat Pump
LanguageEnglish

Related product manuals