EasyManua.ls Logo

Trane 2TTA2 Series User Manual

Trane 2TTA2 Series
8 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
Page #1 background imageLoading...
Page #1 background image
ALL phases of this installation must comply with NATIONAL, STATE AND LOCAL CODES
IMPORTANT This Document is customer property and is to remain with this unit. Please return to service information
pack upon completion of work.
Installer’s Guide
Condensing Units
2TTA2, 2TTA0
These instructions do not cover all variations in
systems nor provide for every possible contingency to
be met in connection with installation. All phases of
this installation must comply with NATIONAL, STATE
AND LOCAL CODES. Should further information be
desired or should particular problems arise which are not
covered sufficiently for the purchaser’s purposes, the matter
should be referred to your installing dealer or local distributor.
A. GENERAL
The following instructions cover 2TTA2 and 2TTA0; Con-
densing Units.
NOTICE:
These outdoor units may be used with indoor units
equipped with Thermostatic Expansion Valve or Accutron
Flow Control Check Valve (F.C.C.V.) assembly for refrigerant
flow control only.
Check for transportation damage after unit is uncrated.
Report promptly, to the carrier, any damage found to the unit.
To determine the electrical power requirements of the unit,
refer to the nameplate of the unit. The electrical power
available must agree with that listed on the nameplate.
B. LOCATION & PREPARATION OF THE UNIT
1. When removing unit from the pallet, notice the tabs on
the basepan. Remove tabs by cutting with a sharp tool as
shown in Figure 2 (see page 2).
2. The unit should be set on a level support pad at least as
large as the unit base pan, such as a concrete slab. If this
is not the application used please refer to application
bulletin “Trane APB2001-02”.
3. The support pad must NOT be in direct contact with any
structure. Unit must be positioned a minimum of 12"
from any wall or surrounding shrubbery to insure
adequate airflow. Clearance must be provided in front of
control box (access panels) & any other side requiring
service access to meet National Electrical Code. Also,
the unit location must be far enough away from any
structure to prevent excess roof run-off water from
pouring directly on the unit. Do not locate unit(s) close to
bedroom(s).
4. The top discharge area must be unrestricted for at least
five (5) feet above the unit.
1
5. When the outdoor unit is mounted on a roof, be sure the
roof will support the unit’s weight. Properly selected
isolation is recommended to prevent sound or vibration
transmission to the building structure.
6. The maximum length of refrigerant lines from outdoor to
indoor unit should NOT exceed sixty (60) feet.
7. If outdoor unit is mounted above the air handler, maxi-
mum lift should not exceed sixty (60) feet (suction line).
If air handler is mounted above condensing unit, maxi-
mum lift should not exceed sixty (60) feet (liquid line).
NOTE:
Refer to Refrigerant Piping Software Pub. No. 32-3312-02.
8. Locate and install indoor coil or air handler in accor-
dance with instruction included with that unit.
5 FT. ABOVE UNIT-UNRESTRICTED
2TTA2-IN-1B
18-AC51D3-3
Question and Answer IconNeed help?

Do you have a question about the Trane 2TTA2 Series and is the answer not in the manual?

Trane 2TTA2 Series Specifications

General IconGeneral
BrandTrane
Model2TTA2 Series
CategoryHeat Pump
LanguageEnglish

Summary

Condensing Units Installation Guide

General Unit Information

Covers general instructions and notices for 2TTA2 and 2TTA0 condensing units.

Unit Location and Preparation

Guidelines for selecting a suitable location and preparing the installation site.

Accutron Flow Control Valve

Details on changing the Accutron orifice size for optimal system performance.

Installing Refrigerant Lines

Instructions for running, bending, and securing refrigerant tubing.

Service Valve Operation

Operation procedures for brass liquid and gas line service valves.

Brazing Refrigerant Lines

Steps and precautions for brazing refrigerant lines to service valves.

System Evacuation and Charging

Procedures for evacuating the system and charging with HCFC-22.

Electrical Connections and Wiring

Compressor Start-Up Procedure

Steps to safely activate the compressor sump heat and start the system.

Operational and Checkout Procedures

Overview of final checks and operational procedures for proper system performance.

Electric Heater Installation

Instructions for installing electric heaters in the air handling device.

Outdoor Thermostat Installation

Information on field installation of an outdoor thermostat.

Seacoast Shield Installation

Guidance on installing the seacoast kit for units near salt water.

Typical Field Hook-Up Diagrams

Illustrations of common wiring configurations for various system setups.

Troubleshooting Guide

Unit Dimensions and Mounting

Outline Drawing and Dimensions

Provides outline drawings and detailed dimensions for various unit models.

Mounting Hole Locations

Diagrams showing mounting hole positions for different base types.

Checkout Procedure

System Checkout Checklist

A list of checks to perform after installation is completed for system verification.

Component Operation Checkout

Table detailing component operation based on indoor thermostat settings.

Related product manuals