104
4MXC2324BF0W0AA
PCB code 0151800208CF (manufactured after 6th May 2021)
SW3-5 SW3-6 SW3-7 SW3-8
Indoor unit Address
(Indoor unit address for one wired
controller control more than one
unit)
OFF OFF OFF OFF 0 (master)
OFF OFF OFF ON 1(slave)
OFF OFF ON OFF 2(slave)
OFF OFF ON ON 3(slave)
OFF ON OFF OFF 4(slave)
OFF ON OFF ON 5(slave)
OFF ON ON OFF 6(slave)
OFF ON ON ON 7(slave)
ON OFF OFF OFF 8(slave)
ON OFF OFF ON 9(slave)
ON OFF ON OFF 10(slave)
ON OFF ON ON 11(slave)
ON ON OFF OFF 12(slave)
ON ON OFF ON 13(slave)
ON ON ON OFF 14(slave)
ON ON ON ON 15(slave)
Wired controller communication address
SW3-2 SW3-3 Unit Type
ON ON Cassette
SW1 (1-ON, 0-OFF)
Capacity (SW1-1→SW1-3)
Room
card
SW1-4
Running
mode
Fresh air
/Trouble alarm
Filter
remindng
Location
Description
SW1-1 SW1-2 SW1-3 SW1-5 SW1-6 SW1-7 SW1-8
1 0 1 --- --- --- --- --- Capacity: 10.5kW
0 1 1 --- --- --- --- --- Capacity: 12.5kW
1 1 1 --- --- --- --- --- Capacity: 14.0kW
1 1 1 --- --- --- 1 --- Capacity: 16.0kW
--- --- --- 0 --- --- --- --- Room card invalid (default)
--- --- --- 1 --- --- --- --- Room card valid
--- --- --- --- 0 --- --- --- Heat pump (default)
--- --- --- --- 1 --- --- --- Cooling only
--- --- --- --- --- 0 --- --- Fresh air function
--- --- --- --- --- 1 --- --- Trouble alarm
--- --- --- --- --- --- 0 --- Without lter reminding
--- --- --- --- --- --- 1 --- With lter reminding
--- --- --- --- --- --- --- 0 Used in American
--- --- --- --- --- --- --- 1
Not used in
American(default)