Section 18. Pressure Curves
PRESSURE CURVES (Refer below table for models)
OUTDOOR TEMPERATURE (Degree F)
OUTDOOR TEMPERATURE (Degree F)
COOLING PERFORMANCE CAN BE CHECKED WHEN THE OUTDOOR TEMP IS ABOVE 65 DEG F.
TO CHECK COOLING PERFORMANCE, SELECT THE PROPER INDOOR CFM, ALLOW PRESSURES TO STABILIZE. MEASURE INDOOR WET BULB
TEMPERATURE, OUTDOOR TEMPERATURE, LIQUID AND SUCTION PRESSURES. ON THE PLOTS LOCATE OUTDOOR TEMPERATURE (1);
LOCATE INDOOR WET BULB (2); FIND INTERSECTION OF OD TEMP. & ID W.B. (3); READ LIQUID (4) OR SUCTION (5) PRESSURE IN LEFT COLUMN .
EXAMPLE: (1) OUTDOOR TEMP. 82 F.
(2) INDOOR WET BULB 67 F.
(3) AT INTERSECTION ACTUAL:
(4) LIQUID PRESSURE @ 600 CFM IS 310 PSIG LIQUID PRESSURE SHOULD BE +/- 10 PSI OF CHART
(5) SUCTION PRESSURE @ 600 CFM IS 141 PSIG SUCTION PRESSURE SHOULD BE +/- 3 PSIG OF CHART
115
120
125
130
135
140
145
150
155
160
165
170
50 60 70 80 90 100110 120
(1)
170
220
270
320
370
420
470
520
50 60 70 80 90 100110 120
(1)
(3)
(3)
(5)
(4)
(2)
(2)
INDOOR ENTERING
WET BULB CURVES
TOP TO BOTTOM
71, 67, 63 AND 59 DEG F.
INDOOR ENTERING
WET BULB CURVES
TOP TO BOTTOM
71, 67, 63 AND 59 DEG F.
Cooling
@SCFM
A4AC6036B1
A4AC6037B1
OD Model
1000
950
A4AC6042B1 1250
71
63
67
59
LIQUID PRESSURE (PSIG)
SUCTION PRESSURE (PSIG)