A5HL5-SF-1A-EN
Parameter Code Value Description
S03
0 The unit will stop Cooling while the system low pressure detected lower than 94.3psi.
(Default)
1 The unit will stop Cooling while the system low pressure detected lower than 87.1psi.
2 The unit will stop Cooling while the system low pressure detected lower than 78.9psi.
3 The unit will stop Cooling while the system low pressure detected lower than 71.7psi.
4 The unit will stop, when the system detect the low pressure is lower than 64.5psi.
5 The unit will stop Cooling while the system low pressure detected lower than 50.1psi.
SSeettttiinngg PPaarraammeetteerr SSeettttiinnggss