Pressure Curves
COOLING PERFORMANCE CAN BE CHECKED WHEN THE OUTDOOR TEMP IS ABOVE 65 DEG F.
TO CHECK COOLING PERFORMANCE, SELECT THE PROPER INDOOR CFM, ALLOW PRESSURES TO
STABILIZE. MEASURE INDOOR WET BULB TEMPERATURE, OUTDOOR TEMPERATURE, DISCHARGE
AND SUCTION PRESSURES. ON THE PLOTS LOCATE OUTDOOR TEMPERATURE (1); LOCATE INDOOR
WET BULB (2); FIND INTERSECTION OF OD TEMP. & ID W.B. (3); READ DISCHARGE OR SUCTION
PRESSURE IN LEFT COLUMN (4).
EXAMPLE: (1) OUTDOOR TEMP. 82 F.
(2) INDOOR WET BULB 67 F.
(3) AT INTERSECTION
(4) DISCHARGE PRESSURE @ 865 CFM IS 320 PSIG.
(5) SUCTION PRESSURE @ 865 CFM IS 134 PSIG.
ACTUAL: DISCHARGE PRESSURE SHOULD BE +/- 10 PSI OF CHART
SUCTION PRESSURE SHOULD BE +/- 3 PSIG OF CHART
LIQUID PRESSURE (PSIG)
OUTDOOR TEMPERATURE (Degree F)
SUCTION PRESSURE (PSIG)
OUTDOOR TEMPERATURE (Degree F)
LIQUID PRESSURE (PSIG)
OUTDOOR TEMPERATURE (Degree F)
SUCTION PRESSURE (PSIG)
OUTDOOR TEMPERATURE (Degree F)
Cooling@SCFM
865
Heating@SCFM
980
170
220
270
320
370
420
470
520
60 70 80 90 100 110 120
INDOOR ENTERING WET BULB
CURVES TOP TO BOTTOM
71,67,63 AND 59 DEGF.
(2)
(1)
(4)
(3)
200
250
300
350
400
450
500
-10 0 10 20 30 40 50 60 70 80
INDOOR ENTERING WET
BULB CURVESTOP TO
BOTTOM 80, 70 AND 60 DEG
F.
90
100
110
120
130
140
150
160
170
180
60
70
80
90 100 110 120
INDOOR ENTERING WET
BULB CURVES TOP TO
BOTTOM 71,67,63 AND 59
DEGF.
71
67
63
59
(1)
(2)
(3)
(5)
0
20
40
60
80
100
120
140
160
180
-10 0 10 20 30 40 50 60 70 80
INDOOR ENTERING WET BULB
CURVESTOP TO BOTTOM 80,
70 AND 60 DEG F.
PRESSURE CURVES for A5HL5024A1