EasyManua.ls Logo

Trane A5HL5060A1000A - Page 46

Trane A5HL5060A1000A
52 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
46
A5HL5-SF-1A-EN
F7 - Module Temperature Protection
IPM overtemperature protection, when IPM temperature more than 203°F, it will show F7.
Replace ODU PCB
IPM temperature
circuit abnormal?
Replace capillary
Display F7
End
IPM well contact
No
to heat sink?
Any dust or gap btw
IPM & heat sink?
Yes
Yes
ODU cooling system
abnormal? Compressor
with high running current?
(24/36K 13-16A,
48/60K
16-20A)
No
Check the screws
fully fasten?
No
Yes
Fasten the screw
Yes
F7 disappear?
No
Low pressure normal?
(116-174psi)
No
Yes
Yes
No
No
Is the 2way and 3way
valve fully opened?
Yes
Yes
Capillary blocked?
No
No
No
F7 disappear?
Yes
Yes
Condenser /
evaporator dirty?
End
Clean condenser /
evaporator
Open the valve
Clean or adjust the gap
btw IPM and heat sink

Related product manuals