88-A5PA3001-1A-EN
21
Table 9. Filter Sizes (field supplied filter rack)
UNIT
NOMINAL
CFM
FILTER
(a)
SIZE
(Sq Ft)
FILTER
RESISTANCE
(“W.C.)
A5PA3024 800 2.67 0.08
A5PA3030 1000 3.33 0.08
A5PA3036 1200 4.00 0.08
A5PA3042 1400 4.67 0.08
A5PA3048 1600 5.33 0.08
A5PA3060 2000 6.67 0.08
(a)
Filters must be installed in the return air system. The above square
footages are based on 300 F.P.M. face velocity. If permanent filters
are used, size per mfg. Recommendation with clear resistance of
0.05”WC.
IImmppoorrttaanntt:: Air filters and media wheels or plates shall
meet the test requirements in UL 900.
Electrical Wiring
NNoottee:: This unit is factory wired for 230V. See wiring
diagram for 208V conversion.
EElleeccttrriiccaall CCoonnnneeccttiioonnss
Electrical wiring and grounding must be installed in
accordance with local codes or, in the absence of local
codes, with the National Electrical Code ANSI/NFPA 70,
Latest Revision.
EElleeccttrriiccaall PPoowweerr
It is important that proper electrical power be available
for the unit. Voltage variation should remain within the
limits stamped on the unit nameplate.
DDiissccoonnnneecctt SSwwiittcchh
Provide an approved weatherproof disconnect within
close proximity and wwiitthhiinn ssiigghhtt ooff tthhee uunniitt.. If
disconnect must be mounted to the cabinet, the
location shown in Table 12, p. 21 should be the only
one considered.
OOvveerr CCuurrrreenntt PPrrootteeccttiioonn
The branch circuit feeding the unit must be protected
as shown on the unit's rating plate.
PPoowweerr WWiirriinngg
The power supply lines must be run in weather-tight
conduit to the disconnect and into the side of the unit
control box. Provide strain relief for all conduit with
suitable connectors.
Provide flexible conduit supports whenever vibration
transmission may cause a noise problem within the
building structure.
1. Remove the Control/Heat access panel. Pass the
power wires through the Power Entry hole in the
end of the unit. See Table 10, p. 21.
2. Connect the high voltage wires to the appropriate
contactor terminals. Single phase units use a two
(2) pole contactor and three phase units use three
(3) pole contactor. Connect the ground to the
ground lug on the chassis. See Table 12, p. 21.
Ensure all connections are tight.
Table 10. Power Wiring
Run power supply lines through weather-tight
conduit and secure to unit with strain relief.
Table 11. Power Connections
Unit Ground
Lug
Contactor
Table 12. Mounted Disconnect Location
UUnniitt IInnssttaallllaattiioonn