AFC
Fault LED Description
OFF No Fault
Solid On Internal control failure
1 24VAC fuse blown
2
PM Data Corrupt or Missing / Motor Mismatch
4 Blower communication error
5
Internal communication error (refer to Unit LED on EVC, EHC, HHC)
(1)(2)
11
EVC has detected a fault condition (refer to Fault LED on EVC)
12 EHC / HHC has detected a fault condition (refer to Fault LED on EHC / HHC)
1) If Unit LED on AFC is flashing 2 times/second, AFC is causing the error.
2) Unit LED on suspect control will flash 2 times/second. All LED's will be off if power is not applied.