7 AM7A0C36H31-SF-1A
Dip Switch S1
Set the S1-1 and S1-2 dip switches for the OD •
multiplier (tonnage) per the chart.
Set the S1-3 dip switch for AC or HP. •
S1
Airflow Control (AFC)
1
1
1 2 3 4 5
1 2 3 4 5
HP
2(Compressor)
2(Stages)
AC (System)
}
OUTDOOR
Capacity (Tons)
OUTDOOR
}
Torque
CFM/Ton
Cool OffDelay
}
INDOOR
CFM
+12V
R13
R14
R1
R4
1
U1
RNET 1
S1
on
on
S2
RNET 2
R
6
C22
C19
C
15
C
12
C18
C21
C10
D9
L1
R22
Set the S1-4 dip switch for the number of stages •
on the outdoor unit.
Set the S1-5 dip switch for the number of •
compressors.
#COMPRESSORS S1‐5
1 OFF
2 ON
16 SEER = 1 Compressor
19 SEER = 2 Compressors
20 SEER = 2 Compressors
16 SEER = 2 Stages
19 SEER = 2 Stages
20 SEER = 2 Stages
INDOORMODEL S1‐1 S1‐2 ODMULTIPLIER
OFF OFF 3
OFF ON 2
ON OFF 2.5
ON ON 3.5
*Maybe"A"or"T"
*AM7A0C36H31SA
NOTE:TheODmultiplierinconjuctionwiththeCFM/TONcan
beusedtoadjusttotalairflowforyourapplication.Example:
4.5Tx370CFM/TON=1665CFM