EasyManua.ls Logo

Trane Axiom GEHB 006 - Installation - Blower Motor; Blower Motor Speed-Tap Retrofit

Trane Axiom GEHB 006
96 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
58 WSHP-SVX01E-EN
Installation
Blower Motor Speed-Tap
Retrofit
Note: (for 1/2 Through 5 Ton Units
ONLY)
Motors installed in the unit include 4-
speed and 3-speed configurations.
All voltages include a 4-speed
configuration, with the exception of
380V, 415V, 460V which contain a 3-
speed arrangement and 575V which
contains a 2-speed arrangement. To
modify the rpm of the motor, the
following steps may be followed.
WARNING
Hazardous Voltage!
Disconnect all electric power,
including remote disconnects before
servicing. Follow proper lockout/
tagout procedures to ensure the
power can not be inadvertently
energized. Failure to disconnect
power before servicing could result
in death or serious injury.
WARNING!
Grounding Required!
Follow proper local and state
electrical code on requirements for
grounding. Failure to follow code
could result in death or serious
injury.
1. Remove service access panel at
the unit front.
2. Find the blower motor relay. The
relay is highlighted below. The
relay location is consistent in all
control configurations.
Figure 64. Service access panel
3. For units w/o Hot Gas Reheat
Remove undesired speed-tap
wire from 1K4 relay at spade 3.
Wire tie the lead, to eliminate a
short.
For units with Hot Gas
Reheat Remove undesired
speed-tap wire from 1K8 relay at
spade 6. Wire tie the lead, to
eliminate a short.
4. For units w/o Hot Gas Reheat
Select desired speed-tap wire.
Connect desired speed tap wire
to 1K4 relay at spade 3.
For units with Hot Gas
Reheat Select desired speed-tap
wire. Connect desired speed tap
wire to 1K8 relay at spade 6.
Figure 65. Relay location
Figure 66. Wiring change
5. Install service front panel.
Reconnect power to the unit.
Note: When using the medium or
low speed tap, the purple
wire must be jumpered to the
high speed tap (blk).
Figure 67.
Figure 68. Service access panel
Table 35. 4-Speed Motor (115, 208, 230,
265)
Lead Colors
Lead Black Blue Orange Red
Speed High Medium
High
Medium
Low
Low
Table 36. 3-Speed Motor (380, 415, 460)
Lead Colors
Lead Black Blue Orange
Speed High Medium Low
Table 37. 2-Speed Motor (575)
Lead Colors
Lead Black Blue
Speed High Low

Table of Contents