EasyManua.ls Logo

Trane Axiom GEHB 006 - Page 68

Trane Axiom GEHB 006
96 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
68 WSHP-SVX01E-EN
Electrical Requirements
060
208/60/1 33.4 28.00 169.0 1 39.0 5.40 1 1 40.4 60 0 0
208/60/1 36.7 28.0 169.0 1 39.0 5.4 1 1 45.9 60 6.50 31.3
230/60/1 33.4 28.00 169.0 1 35.0 5.40 1 1 40.4 60 0 0
230/60/1 40.2 28.0 169.0 1 39.0 5.4 1 1 50.3 60 8.00 34.8
208/60/3 25.4 20.00 123.0 1 28.0 5.40 1 1 30.4 50 0 0
208/60/3 25.4 20.0 123.0 1 27.0 5.4 1 1 30.4 50 6.50 18.0
230/60/3 25.4 20.00 123.0 1 28.0 5.40 1 1 30.4 50 0 0
230/60/3 25.5 20.0 123.0 1 27.0 5.4 1 1 31.9 50 8.00 20.1
380-415/50/3 12.8 10.00 62.0 1 14.0 2.70 1 1 15.2 25 0 0
380-415/50/3 14.7 10.0 62.0 1 14.0 2.7 1 1 18.4 25 8.60 12.0
460/60/3 10.2 7.50 49.5 1 10.5 2.70 1 1 12.1 15 0 0
460/60/3 16.0 7.5 49.5 1 10.5 2.7 1 1 20.0 25 10.60 13.3
575/60/3 8.6 6.40 40.0 1 9.0 2.20 1 1 10.2 15 0 0
GEH
072
208/60/1 38.6 16.00 82.0 2 22.4 6.55 1 1 42.6 50
230/60/1 38.5 16.00 82.0 2 22.4 6.47 1 1 42.5 50
208/60/1 41.3 16.00 82.0 2 22.4 9.34 1.5 1 45.3 60
230/60/1 40.9 16.00 82.0 2 22.4 8.94 1.5 1 44.9 60
208/60/1 43.2 16.00 82.0 2 22.4 11.20 2 1 47.2 60
230/60/1 42.2 16.00 82.0 2 22.4 10.23 2 1 46.2 60
380-415/50/3 12.9 6.40 42.0 2 8.9 1.70 0.75 1 14.5 20
208/60/3 24.3 10.40 65.5 2 14.6 3.50 1 1 26.9 35
230/60/3 24.6 10.40 65.5 2 14.6 3.80 1 1 27.2 35
380-415/50/3 13.3 6.40 42.0 2 8.9 2.10 1 1 14.9 20
460/60/3 11.6 4.90 33.0 2 6.9 1.80 1 1 12.8 15
208/60/3 26.4 10.40 65.5 2 14.6 5.60 1.5 1 29.0 35
230/60/3 25.6 10.40 65.5 2 14.6 4.80 1.5 1 28.2 35
380-415/50/3 14.2 6.40 42.0 2 8.9 3.00 1.5 1 15.8 20
460/60/3 23.5 4.90 33.0 2 6.9 2.40 1.5 1 13.4 15
208/60/3 27.9 10.40 65.5 2 14.6 7.10 2 1 30.5 40
230/60/3 27.0 10.40 65.5 2 14.6 6.20 2 1 29.6 40
380-415/50/3 14.6 6.40 42.0 2 8.9 3.40 2 1 16.2 20
460/60/3 12.9 4.90 33.0 2 6.9 3.11 2 1 14.1 15
380-415/50/3 16.7 6.40 42.0 2 8.9 5.50 3 1 18.3 25
Table 41. Electrical performance continued
Model
No. Volts
Total
FLA
Comp
RLA
(ea)
Comp
LRA
(ea)
No. of
Compr
es.
Cmp
MCC
Blower
Motor
FLA
Blower
Motor
HP
Fan
Motor
Num
Min
Circuit
Amps
Max
Overcurrent
Protective
Device
Electric
Heat
kW
Electric
Heat
Amps

Table of Contents

Related product manuals