74 WSHP-SVX01E-EN
Electrical Requirements
GEH
180
208/60/3 57.1 25.00 164.0 2 35.0 7.10 2 1 63.4 80
230/60/3 56.2 25.00 164.0 2 35.0 6.20 2 1 62.5 80
460/60/3 27.1 12.00 100.0 2 17.0 3.11 2 1 30.1 40
575/60/3 20.9 9.30 78.0 2 13.0 2.30 2 1 23.2 30
208/60/3 59.4 25.00 164.0 2 35.0 9.40 3 1 65.7 90
230/60/3 58.2 25.00 164.0 2 35.0 8.20 3 1 64.5 80
460/60/3 28.1 12.00 100.0 2 17.0 4.10 3 1 31.1 40
575/60/3 21.9 9.30 78.0 2 13.0 3.30 3 1 24.2 30
208/60/3 66.0 25.00 164.0 2 35.0 16.00 5 1 72.3 90
230/60/3 64.0 25.00 164.0 2 35.0 14.00 5 1 70.3 90
460/60/3 31.0 12.00 100.0 2 17.0 7.00 5 1 34.0 45
575/60/3 23.8 9.30 78.0 2 13.0 5.20 5 1 26.1 35
208/60/3 75.0 25.00 164.0 2 35.0 25.00 7.5 1 81.3 100
230/60/3 71.6 25.00 164.0 2 35.0 21.60 7.5 1 77.9 100
460/60/3 34.8 12.00 100.0 2 17.0 10.80 7.5 1 37.8 45
575/60/3 26.8 9.30 78.0 2 13.0 8.20 7.5 1 29.1 35
GEV
180
208/60/3 59.4 25.00 164.0 2 35.0 9.40 3 1 65.7 90
230/60/3 58.2 25.00 164.0 2 35.0 8.20 3 1 64.5 80
380-420/50/3 27.4 12.00 90.5 2 17.0 3.40 2 1 30.4 40
460/60/3 28.1 12.00 100.0 2 17.0 4.10 3 1 31.1 40
575/60/3 21.9 9.30 78.0 2 13.0 3.30 3 1 24.2 30
208/60/3 66 25.00 164.0 2 35.0 16.00 5 1 72.3 90
230/60/3 64 25.00 164.0 2 35.0 14.00 5 1 70.3 90
380-420/50/3 29.5 12.00 90.5 2 17.0 5.50 3 1 32.5 40
460/60/3 31 12.00 100.0 2 17.0 7.00 5 1 34.0 45
575/60/3 23.8 9.30 78.0 2 13.0 5.20 5 1 26.1 35
208/60/3 75 25.00 164.0 2 35.0 25.00 7.5 1 81.3 100
230/60/3 71.6 25.00 164.0 2 35.0 21.60 7.5 1 77.9 100
380-420/50/3 33.3 12.00 90.5 2 17.0 9.30 5 1 36.3 45
460/60/3 34.8 12.00 100.0 2 17.0 10.80 7.5 1 37.8 45
575/60/3 26.8 9.30 78.0 2 13.0 8.20 7.5 1 29.1 35
Table 41. Electrical performance continued
Model
No. Volts
Total
FLA
Comp
RLA
(ea)
Comp
LRA
(ea)
No. of
Compr
es.
Cmp
MCC
Blower
Motor
FLA
Blower
Motor
HP
Fan
Motor
Num
Min
Circuit
Amps
Max
Overcurrent
Protective
Device
Electric
Heat
kW
Electric
Heat
Amps