ACC-SVN67D-EN 15
Electrical Data
480 Volts Three Phase
6 TSC072E4 BAYHTRS409* 9.0 1 18.2 25 18.8 25
6 TSC072E4 BAYHTRS418* 18.0 1 30.3 35 31.0 35
6 TSC072E4 BAYHTRS427* 27.0 2 43.8 45 44.5 45
6 TSC072E4 BAYHTRS436* 36.0 2 57.3 60 58.0 60
TSC090E4 BAYHTRW409* 9.0 1 19.5 30 22.4 35
TSC090E4 BAYHTRW418* 18.0 1 29.3 30 32.9 35
TSC090E4 BAYHTRW427* 27.0 2 42.8 45 46.4 50
TSC090E4 BAYHTRW436* 36.0 2 56.3 60 59.9 60
(2)
TSC092E4 BAYHTRT409* 9.0 1 21.5 25 23.0 30
(2)
TSC092E4 BAYHTRT418* 18.0 1 31.0 35 32.9 35
(2)
TSC092E4 BAYHTRT427* 27.0 2 44.5 45 46.4 50
(2)
TSC092E4 BAYHTRT436* 36.0 2 58.0 60 59.9 60
TSC102E4 BAYHTRT409* 9.0 1 21.9 25 23.4 30
TSC102E4 BAYHTRT418* 18.0 1 31.0 35 32.9 35
TSC102E4 BAYHTRT427* 27.0 2 44.5 45 46.4 50
TSC102E4 BAYHTRT436* 36.0 2 58.0 60 59.9 60
10 TSC120E4 BAYHTRA418* 18.0 1 32.5 35
10 TSC120E4 BAYHTRA427* 27.0 2 46.0 50
10 TSC120E4 BAYHTRA436* 36.0 2 59.5 60
10 TSC120E4 BAYHTRA454* 54.0 2 70.4 80
575 Volts Three Phase
6 TSC072EW BAYHTRSW09* 9.0 1 13.0 20 14.0 20
6 TSC072EW BAYHTRSW18* 18.0 1 23.8 25 24.8 25
6 TSC072EW BAYHTRSW27* 27.0 2 34.6 35 35.6 40
6 TSC072EW BAYHTRSW36* 36.0 2 45.4 50 46.4 50
TSC090EW BAYHTRWW18* 18.0 1 23.4 25
TSC090EW BAYHTRWW27* 27.0 2 34.3 35
TSC090EW BAYHTRWW36* 36.0 2 45.0 45
(2)
TSC092EW BAYHTRTW18* 18.0 1 24.8 25 26.3 30
(2)
TSC092EW BAYHTRTW27* 27.0 2 35.6 40 37.1 40
(2)
TSC092EW BAYHTRTW36* 36.0 2 46.4 50 47.9 50
TSC102EW BAYHTRTW18* 18.0 1 24.8 25 26.3 30
TSC102EW BAYHTRTW27* 27.0 2 35.6 40 37.1 40
TSC102EW BAYHTRTW36* 36.0 2 46.4 50 47.9 50
10 TSC120EW BAYHTRAW18* 18.0 1 27.0 30
10 TSC120EW BAYHTRAW36* 36.0 2 48.6 50
10 TSC120EW BAYHTRAW54* 54.0 2 57.4 60
(1) No optional motors available for 3-5 tons. The standard motor for 1-phase models is a Multispeed, Direct Drive Motor. The Standard Motor for the 3-
phase models is a Belt Drive Motor.
(2) Dual refrigeration system.
Table 4. Unit wiring with electric heat (single point connection) - standard efficiency (continued)
Standard Indoor Motor Oversized Indoor Motor
Tons
Unit Model
Number
Heater Model
Number
Heater kW
Rating
(1)
Control
Stages MCA
Max Fuse Size or
Max Circuit
Breaker MCA
Max Fuse Size or
Max Circuit
Breaker