18 ACC-SVN67D-EN
Electrical Data
Table 7. Air temperature rise 380/415 Volt (50 hz)
(Degrees C)
7
(Degrees F)
8
6 Ton 7.5 Ton 10 Ton 6 Ton 7.5 Ton 10 Ton
4100
M
3
/H
5100
M
3
/H
6800
M
3
/H
2400CF
M
3000CF
M
4000CF
M
kW Voltage Stages
WSC072
ED
WSC090
ED
WSC120
ED kW Voltage Stages
WSC072
ED
WSC090
ED
WSC120
ED
11.3 380-415/50/3 1 8.3 6.6 --- 11.3 380-415/50/3 1 14.9 11.9 ---
12.5 380-415/50/3 1 9.1 7.3 --- 12.5 380-415/50/3 1 16.5 13.2 ---
13.5 380-415/50/3 1 9.9 7.9 --- 13.5 380-415/50/3 1 17.8 14.2 ---
16.9 380-415/50/3 2 12.4 9.9 7.4 16.9 380-415/50/3 2 22.3 17.8 13.4
18.8 380-415/50/3 2 13.8 11.0 8.3 18.8 380-415/50/3 2 24.8 19.8 14.9
20.2 380-415/50/3 2 14.8 11.8 8.9 20.2 380-415/50/3 2 26.6 21.3 16.0
22.6 380-415/50/3 2 16.5 13.2 9.9 22.6 380-415/50/3 2 29.8 23.8 17.9
25.0 380-415/50/3 2 18.3 14.6 11.0 25.0 380-415/50/3 2 32.9 26.3 19.8
26.9 380-415/50/3 2 19.7 15.7 11.8 26.9 380-415/50/3 2 35.4 28.3 21.3
33.9 380-415/50/3 2 --- --- 14.9 33.9 380-415/50/3 2 --- --- 26.8
37.5 380-415/50/3 2 --- --- 16.5 37.5 380-415/50/3 2 --- --- 29.6
40.4 380-415/50/3 2 --- --- 17.7 40.4 380-415/50/3 2 --- --- 31.9
6. For minimum design airflow, see performance table for each unit.
7. To calculate the temperature rise in Celsius at different airflow, use the following formula: Temperature rise (C) across electric heater = (kW x 2985)/
(M3 / H).
8. To calculate the temperature rise in Fahrenheit at different airflow, use the following formula: Temperature rise (F) across electric heater = (kW x 3414)/
(1.08 / H).
Table 8. Air temperature rise 380/415 Volt (50 hz)
(Degrees C)
10
(Degrees F)
11
6 Ton
7.5
Ton
8.5
Ton 10 Ton 6 Ton 7.5 Ton 8.5 Ton 10 Ton
4100
M
3
/ H
5100
M
3
/ H
5800
M
3
/ H
6800
M
3
/ H
2400CF
M
3000CF
M
3400CF
M
4000CF
M
Kw Voltage Stages
TSC07
2ED
TSC09
0ED
TSC10
2ED
TSC12
0ED KW Voltage Stages
TSC072
ED
TSC090
ED
TSC102
ED
TSC120
ED
11.3 /
13.5
380-
415/50/3
1
8.3 /
9.9
6.6 /
7.9
--- ---
11.3 /
13.5
380-
415/50/3
1
14.9 /
17.8
11.9 /
14.2
--- ---
16.9 /
20.2
380-
415/50/3
2
12.4 /
14.8
9.9 /
11.8
8.7 /
10.4
7.4 /
8.9
16.9 /
20.2
380-
415/50/3
2
22.3 /
26.6
17.8 /
21.3
15.7 /
18.8
13.4 /
16.0
22.6 /
26.9
380-
415/50/3
2
16.5 /
19.7
13.2 /
15.7
11.7 /
13.9
9.9 /
11.8
22.6 /
26.9
380-
415/50/3
2
29.8 /
35.4
23.8 /
28.3
21.0 /
25.0
17.9 /
21.3
33.8 /
40.4
380-
415/50/3
2 --- --- ---
14.8 /
17.7
33.8 /
40.4
380-
415/50/3
2 --- --- ---
26.7 /
31.9
9. For minimum design airflow, see performance table for each unit.
10.To calculate the temperature rise in Celsius at different airflow, use the following formula: Temperature rise (C) across electric
heater = (kW x 2985)/(M3 / H).
11.To calculate the temperature rise in Fahrenheit at different airflow, use the following formula: Temperature rise (F) across electric
heater = (kW x 3414)/(1.08 / H).