ELECTRICAL DATA
Table 2 - Electrical Data
60Hz
Electrical
Power
(V/Hz/Ph)
220/60/1
220/60/1
220/60/1
220/60/1
220/60/3
380/60/3
220/60/3
380/60/3
220/60/3
380/60/3
220/60/3
380/60/3
220/60/3
380/60/3
220/60/3
380/60/3
220/60/3
380/60/3
Model
Water
Pump
FLA
4.4
4.4
4.4
6.5
2.7
1.6
4.2
2.4
4.2
2.4
5.4
3.1
5.4
3.1
6.0
3.5
9.1
5.3
Comp
1
RLA
14.4
19.4
24.4
24.4
15.3
8.8
23.0
13.3
15.3
8.8
17.4
10.1
23.0
13.2
26.0
15.0
32.4
18.7
Comp
2
RLA
-
-
-
24.4
-
-
-
-
15.3
8.8
17.4
10.1
23.0
13.2
26.0
15.0
32.4
18.7
Fan
1
FLA
2.8
2.8
2.8
4.3
3.0
1.7
3.0
1.7
4.5
2.6
4.5
2.6
3.0
1.7
4.5
2.6
4.5
2.6
Fan
2
FLA
-
-
-
-
-
-
-
-
-
-
-
-
3.0
1.7
4.5
2.6
4.5
2.6
Unit
MCA
25.2
31.5
37.7
65.7
24.8
14.3
36.0
20.7
43.1
24.8
49.1
28.4
63.2
36.2
73.5
42.5
91.0
52.6
Rec.
Fuse
Size
28.8
36.3
43.8
71.8
28.7
16.5
41.7
24.1
47.0
27.0
53.4
31.0
68.9
39.5
80.0
46.2
99.1
57.3
Max
Fuse
Size
39.6
50.9
62.1
90.1
40.1
23.1
59.0
34.0
58.4
33.6
66.5
38.5
86.2
49.4
99.5
57.5
123.4
71.3
030
040
050
100
050
050
075
075
100
100
125
125
150
150
175
175
200
200
50Hz
Electrical
Power
(V/Hz/Ph)
380-415/50/3
380-415/50/3
380-415/50/3
380-415/50/3
380-415/50/3
380-415/50/3
380-415/50/3
Model
Water
Pump
FLA
1.1
1.4
1.4
1.7
1.7
2.0
2.8
Comp
1
RLA
7.4
11.6
7.4
8.7
11.6
13.0
15.1
Comp
2
RLA
-
-
7.4
8.7
11.6
13.0
15.1
Fan
1
FLA
1.5
1.5
2.2
2.2
1.5
2.2
2.2
Fan
2
FLA
-
-
-
-
1.5
2.2
2.2
Unit
MCA
11.9
17.4
20.3
23.5
30.8
36.5
41.2
Rec.
Fuse
Size
13.7
20.3
22.1
25.7
33.7
39.8
45.0
Max
Fuse
Size
19.3
29.0
27.7
32.2
42.4
49.5
56.3
050
075
100
125
150
175
200
Note:
• All voltages supply must fall within the utilization range of ±10 %
• Minimum Circuit Ampacity (MCA) = Largest Load x 1.25 + Sum of additional Loads. (Used for sizing wire)
• Recommended Fuse Size (REC) = Largest Load x 1.5 + Sum of additional Loads. (Select closest fuse size)
• Maximum Fuse Size (MFS) = Largest Load x 2.25 + Sum of additional Loads. (Select equal or next lower fuse size)