TABLE 3 - Unit Water Flow Rate - 60HZ
60Hz
Model
030
040
050
075
100
125
150
175
200
Minimum Flow
18.5
22.9
30.2
44.9
59.1
74.7
89.5
102.6
120.0
Rated Flow
27.7
34.3
45.3
67.3
88.7
112.0
134.3
154.0
180.0
Maximum Flow
38.8
48.0
63.4
94.2
124.2
150.0
150.0
175.0
240.0
Model
050
075
100
125
150
175
200
Minimum Flow
25.1
37.3
49.1
62.1
74.4
85.5
98.3
Rated Flow
37.7
56.0
73.7
93.3
111.7
128.3
149.0
Maximum Flow
56.6
84.0
110.6
140.0
150.0
160.0
190.0
CGA-SVX01A-EN
Units: LPM
50Hz Units: LPM
UNIT WATER PRESSURE
DROP
Measure the water pressure rise across the
standard unit (with built-in pump). The
Externally Available Head (E.A.H) should
approximate those indicated by the E.A.H.
curves, with the corresponding flow rates.
For units (without built-in pump) with field-
installed pump outside the unit, water
pressure drop across the unit should
approximate those indicated by the Internal
Pressure Loss (I.P.L.) curves, with the
corresponding flow rates.
For standard unit with built-in pump, refer to
the E.A.H. curve for the system hydraulic
design. For optional unit without a built-in
pump, refer to the I.P.L. curves. (Refer to
Figure 6 for hydraulic characteristics of all
models.)