CG-SVX027E-GB
50
4 UNT-PRC002-GB
Technical Data
FWD 08 12 20 30 45
Power supply (V/Ph/Hz) 230/1/50
Capacities
Cooling capacity on water (1) (kW) 5,2 8,3 15 18,8 30,1
Heating capacity on water (2) (kW) 6,3 11,9 18,9 20,9 38,2
Fan motor (type) 2 x direct drive centrifugal
Fan power input (3) (kW) 0,23 0,46 0,65 1,04 1,51
Current amps (3) (A) 1,1 2,2 3,1 4,7 5,5
Start-up amps (A) 3,2 5,5 9,3 14,1 16,5
Air flow
minimum (m
3
/h) 490 980 1400 1800 2700
nominal (m
3
/h) 820 1650 2300 3000 4500
maximum (m
3
/h) 980 1970 2600 3600 5400
Main coil
Water entering/leaving connections (type) ISO R7 rotating female
(Dia) 3/4" 3/4" 1 1/2" 1 1/2" 1 1/2"
Electric heater (accessory for blower only)
Electric power supply (V/Ph/Hz) 230/1/50 230/1/50 or 400/3/50 400/3/50 400/3/50 400/3/50
Heating capacity (kW) 2/4 8 10 12 12
Hot water coil (accessory for blower only)
Heating capacity (4) (kW) 6,3 12 17,4 22,4 34,5
G2 filter (filter box accessory)
Quantity 2 2 2 2 2
Dimensions ( LxWxth) (mm) 386x221x8 486x271x8 586x321x8 586*421*8 586*621*8
G4 filter (filter box accessory)
Quantity - 2 2 2 2
Dimensions ( LxWxth) (mm) - 486x264x48 586x314x48 586*414*48 586*614*48
Condensate pump (accessory) (type) Centrifugal
Water flow - lift height (l/h - mm) 24 - 500
Not available for FWD30 and FWD45
Sound level (L/M/H speed)
Sound pressure level (5) (dB(A)) 36/40/43 38/41/44 46/50/53 47/52/57 47/52/58
Sound power level (5) (dB(A)) 46/50/53 48/51/54 56/60/63 57/62/67 57/62/68
Unit dimensions
Width x Depth (mm) 890 x 600 1090 x 710 1290 x 820 1290 x 970 1290 x 1090
Height (mm) 250 300 350 450 650
Shipped unit dimensions
Width x Depth (mm) 933 x 644 1133 x 754 1333 x 864 1333 x 1008 1333*1133
Height (mm) 260 310 360 460 660
Weight (kg) 32 46 61 76 118
Colour galvanised steel
Recommended fuse size
Unit alone (aM/gI) (A) 8/16 8/16 8/16 8/25 8/25
Unit with electric heater (gI) (A) 16 (2kW),25 (4kW) 40 (230V),3*16 (400V) 3*20 3*25 3*25
(1) Conditions: Water entering/leaving temperature: 7/12 °C, Air inlet temperature 27/19°C DB/WB - Nominal air flow
(2) Conditions: Water entering/leaving temperature: 50/45 °C, Air inlet temperature 20°C DB - Nominal air flow
(3) At high speed with nominal air flow.
(4) Water entering/leaving temperature 90/70 °C, air inlet temperature 20 °C DB, Nominal air flow.
(5) A rectangular glass wool duct 1m50 long is placed on the blower.The measurement is taken in the room containing the blower unit.
Heat exchanger operating limits:
FWD:
*water temperature: max 100° C
*absolute service pressure: min 1 bar/max 11 bars
Accessories - Hot water coil:
*water temperature: min. +2° C/max. 100° C
*absolute service pressure: min 1 bar/max 11 bars
Maintenance
Cleaning Procedures
It is mandatory to clean regularly the coils for a proper
unit operation. Eliminate pollution and other residual
material help to extend the life of the coils and the unit
CAUTION! Equipment Damage! Do not use coil cleaning
agents to clean uncoated CGAX coils. Use clean water
only. Use of coil cleaning agents on uncoated CGAX
coils could cause damage to coils.
Regular coil maintenance, including frequent cleaning-
enhances the unit’s operating efciency by minimizing
compressor head pressure and amperage draw. The
condenser coil (non-coated and e-coated) should be
cleaned at least once each quarter or more if the unit is
located in a “dirty” or corrosive environment. Cleaning
with cleansers or detergents is strongly discouraged due
to the all-aluminum construction; straight water should
prove sufcient. Any breach in the tubes can result in
refrigerant leaks
Important: Only in extreme cases should any type of
chemical cleaner or detergent be used on micro channel
coils. If it becomes absolutely necessary because water
alone did not clean the coil, specify a cleaner that is:
A is pH neutral cleaner.
An alkaline cleaner that is no higher than 8 on
the pH scale.
An acidic cleaner that is no lower than 6 on the
pH scale.
Does not contain any hydrouoric acids.
Be sure to follow the instructions provided with any
cleaner chosen. Keep in mind that it is still MANDATORY
that the coils are thoroughly rinsed with water after the
application of the cleaner even if the instructions specify
a “No Rinse” cleaner. Cleaners or detergents that are
left on the coil due to improper rinsing will signicantly
increase the possibility of corrosion damage on the
micro channel coil.
Note: Quarterly cleaning (or more for harsh
environment) is essential to extend the life of a MCHE
coil and is required to maintain warranty coverage.
Failure to clean a MCHE coil will void the warranty and
may result in reduced efciency and durability in the
environment.
WARNING! Hazardous Voltage! Disconnect all electric
power, including remote disconnects before servicing.
Follow proper lockout/ tagout procedures to ensure the
power cannot be inadvertently energized. Failure to
disconnect power before servicing could result in death
or serious injury.
1. Disconnect Power to the unit.
2. Wear proper personal protection equipment such
as a face shield, gloves and waterproof clothing.
3. Remove enough panels from the unit to gain safe
access to the micro channel coil.
Note: It is better to clean the coil from the opposite
direction of normal air ow (inside of unit out) because
this allows the debris to be pushed out rather than
forced further into the coil.
1. Use a soft brush or vacuum to remove base debris
or surface loaded bers from both sides of the coil.
Note: Remove solid residue is essential to preserve
performance of the coil and avoid corrosion over the
length of the product life.
2. Using a sprayer and water ONLY, clean the coil
following the guidelines below.
a. Sprayer nozzle pressure should not exceed
40 bars.
b. The maximum source angle should not exceed
25 degrees (Figure 22) to the face of the coil.
For best results spray the micro channel
perpendicular to face of the coil.
c. Spray nozzle should be approximately 5 to 10 cm
from the coil surface.
d. Use at least a 15º fan type of spray nozzle.
Figure 14 - Sprayer source angle
To avoid damage from the spray wand contacting the
coil, make sure the 90º attachment does not come in
contact with the tube and n as abrasion to the coil
could result.
Maintenance of Flanges Connection
It is mandatory to apply marine grease all around the
coil ange connections to the piping on a regular basis
(for instance twice a year) to avoid traps of moisture and
dirt in the gasket recess.
Repair / Replacement of Micro
channel Coil
Micro channel coils are considerably more robust in
design than tube and n condenser coils, however they
are not indestructible. When damage or a leak occurs in
the eld, it is possible to temporarily repair the coil until
another coil can be ordered.
If the leak is found to be within the tube area of the coil,
a eld repair kit (KIT16112) is available through your
local Trane parts center. Because of the all-aluminum
construction and aluminum’s high thermal expansion
rate, a leak located at or on the header assembly cannot
be repaired.