Installation: Mechanical
CVGF Rigging
1. Dimensions are in millimeters (mm). Figure 19.
WARNING
Heavy Objects!
Do not use cables (chains or slings) except as shown. Each of the cables (chains or
slings) used to lift the unit must be capable of supporting the entire weight of the unit.
Lifting cables (chains or slings) may not be of the same length. Adjust as necessary for
even unit lift.
Other lifting arrangements may cause equipment or propertyonly damage. Failure to
properly lift unit may result in death or serious injury. See details below.
1. Use a 3600 mm lifting beam and adjust the chains (cables) for an even, level lift.
2. 900 mm recommended clearance above highest point of compressor.
3. Attach safety chains or cables as shown, and without tension. The safety chain is
not used for lifting, but is there to prevent the unit from rolling.
4. More details weight information is available on request.
2. Each chain or cable used to lift the unit must be capable of supporting the entire
weight of the chiller.
3. Use a 3600 mm lifting beam and adjust the chains or cables for an even, level lift.
4. 900 mm recommended clearance above highest point of compressor.
5. Attach safety chains or cables as shown in Figure 20, and without tension. The safety
chain is not used for lifting, but is there to prevent the unit from rolling.
6. More detailed weight information is available upon request.