Installation
22 SO-SVN037A-EN
Installation
Note: Use 12ga wire.
1. At quad relay output LLID 1A5 in the unit control panel,
disconnect wire 42A from terminal 7.
2. Connect wire 42A to RLY02909 terminal 2.
3. Install a wire between LLID 1A5 terminal 7 and RLY02909
terminal 3.
4. Install a wire from RLY02909 terminal 4 and a common
terminal (1X1-17 is typical).
5. Install a wire from a 120v source terminal (1X1-10 is
typical) that is downstream of breaker 1Q4, to RLY02909
terminal 1.
Figure 33. Installed solid state relay
Figure 34. Completed schematic