16
Electrical Data
Model
Power
Supply
(V/Hz/ph)
Full-
load
current
of water
pump
FLA
Rated
current
of No.1
compressor
RLA
Rated
current
of No.2
compressor
RLA
Rated
current
of No.3
compressor
RLA
Rated
current
of No.4
compressor
RLA
Rated
current
of No.1
fan
FLA
Rated
current
of No.2
fan
FLA
Rated
current
of No.3
fan
FLA
Rated
current
of No.4
fan
FLA
Minimum
circuit
current of
unit
MCA
Recommended
fuse
specification
REC
Maximum
specification
of fuse
MFS
Minimum
specification
of copper
core wire
diameter for
power wire
mm
2
CX(G)AJ0455 380/50/3
18.6 18.6 2.1 2.1 46.05 50.70 64.65 16
CX(G)AJ0655 380/50/3
20.8 20.8 2.1 2.1 51.00 56.20 71.80 16
CX(G)AJ1305 380/50/3
20.8 20.8 20.8 20.8 2.1 2.1 2.1 2.1 92.60 97.80 113.40 35