ECM Overview and Setup
UNT-SVX07J-EN 79
Fan Speed Response Verification
1. After performing controller specific commissioning,
observe the display on the motor control board with
the power on, to the unit. The motor control board
display should display a looping status indicator as
follows:
Mtr1 0 Mtr2 0 FSt1 Off
Fst2
Off EhEn On
Notes:
The
EhEn indicator is unit-specific and may indicate
Off” at this point; refer to thermistor function for more
information.
A representative fan speed of “1080 rpm are shown in
the example below. Each unit is factory-configured
differently and will have different settings for different
fan speeds.
2. While the unit remains on, exercise the fan controls on
the unit, either directly or indirectly through request for
unit heat/cool. Observe the fan spinning, and then
observe the fan display on the motor control board. It
should display a looping status indicator as follows:
For a size 200, 300, 400, 600, or 800 unit (using typical
unit operating fan speeds):
Mtr1 1080 Mtr2 0 FSt1 On
Fst2
Off EhEn On
For a size 1000 or 1200 unit (using typical unit
operating fan speeds):
Mtr1 1080 Mtr2 1080 FSt1
On Fst2
on EhEn On
Note: The
EhEn indicator is unit-specific and may
indicate “Off” at this point; refer to thermistor
function for more information.
3. OPTIONAL:
While the fan is running, if practical, change the fan
speeds and observe the display temporarily indicate:
ramp
Exercise all fan speeds to ensure positive unit
response and to validate any field wiring.