Maintenance
WWAARRNNIINNGG
HHaazzaarrddoouuss VVoollttaaggee!!
FFaaiilluurree ttoo ddiissccoonnnneecctt ppoowweerr bbeeffoorree sseerrvviicciinngg ccoouulldd rreessuulltt iinn ddeeaatthh oorr sseerriioouuss iinnjjuurryy..
DDiissccoonnnneecctt aallll eelleeccttrriicc ppoowweerr,, iinncclluuddiinngg rreemmoottee ddiissccoonnnneeccttss bbeeffoorree sseerrvviicciinngg.. FFoollllooww
pprrooppeerr lloocckkoouutt//ttaaggoouutt pprroocceedduurreess ttoo eennssuurree tthhee ppoowweerr ccaann nnoott bbee iinnaaddvveerrtteennttllyy
eenneerrggiizzeedd.. VVeerriiffyy tthhaatt nnoo ppoowweerr iiss pprreesseenntt wwiitthh aa vvoollttmmeetteerr..
WWAARRNNIINNGG
CChheecckk ooff SSaaffeettyy DDeevviicceess RReeqquuiirreedd!!
FFaaiilluurree ttoo ddoo ffoollllooww iinnssttrruuccttiioonnss bbeellooww ccoouulldd ccaauussee uunnssaaffee ccoonnddiittiioonnss aanndd rreessuulltt iinn ddeeaatthh,,
sseerriioouuss iinnjjuurryy oorr pprrooppeerrttyy ddaammaaggee..
AAllll ssaaffeettyy ccoonnttrroollss MMUUSSTT bbee cchheecckkeedd bbeeffoorree ssttaarrttiinngg tthhee uunniitt aanndd dduurriinngg rreegguullaarr
mmaaiinntteennaannccee!! CChheecckk aanndd tteesstt tthhee ooppeerraattiioonnaall ffuunnccttiioonnss ooff aallll ssaaffeettyy ddeevviicceess ssuupppplliieedd wwiitthh
tthhiiss uunniitt..
WWAARRNNIINNGG
HHeeaavvyy OObbjjeecctt!!
FFaaiilluurree ttoo iinnssppeecctt tthhee ssuussppeennssiioonn ccoouulldd rreessuulltt iinn ddeeaatthh oorr sseerriioouuss iinnjjuurryy,, aanndd eeqquuiippmmeenntt
ddaammaaggee..
IInnssppeecctt tthhee ssuussppeennssiioonn aanndd//oorr ssuuppppoorrtt ssyysstteemm ffoorr tthhee mmaakkee--uupp aaiirr uunniitt ttoo eennssuurree tthhaatt aallll
ffaasstteenneerrss aarree ttiigghhtt aanndd tthhee uunniitt iiss sseeccuurree bbeeffoorree wwoorrkkiinngg uunnddeerrnneeaatthh tthhee uunniitt..
• To check gas tightness of the safety shut-off valves, turn off the manual valve upstream of the
appliance combination control. Remove the 1/8" pipe plug on the inlet side of the
combination control and connect a manometer to that tapping. Turn the manual valve on to
apply pressure to the combination control. Note the pressure reading on the manometer,
then turn the valve off. A loss of pressure indicates a leak. If a leak is detected, use a soap
solution to check all threaded connections. If no leak is found, combination control is faulty
and must be replaced before putting appliance back in service.
NNoottee:: Gas tightness of the safety shutoff valves must be checked on at least an annual basis.
• These units have been developed for indoor installation. Maintenance is required and it is
suggested that the following unit servicing and inspections be performed routinely. Also read
in entirety and refer to the Separated Combustion Indoor Duct Furnace Manual for
maintenance requirements.
• Inspect area near unit to be sure that there is no combustible material located within the
minimum clearance requirements (see Figure 15, p. 22). Service panels provide easy access
to the blower compartment and the electrical cabinet. To remove the service door from any of
these compartments, refer to access panel removal section in beginning of this manual.
WWAARRNNIINNGG
CCoommbbuussttiibbllee MMaatteerriiaallss!!
FFaaiilluurree ttoo mmaaiinnttaaiinn pprrooppeerr cclleeaarraannccee bbeettwweeeenn tthhee uunniitt aanndd ccoommbbuussttiibbllee mmaatteerriiaallss ccoouulldd
ccaauussee aa ffiirree wwhhiicchh ccoouulldd rreessuulltt iinn ddeeaatthh oorr sseerriioouuss iinnjjuurryy oorr pprrooppeerrttyy ddaammaaggee..
RReeffeerr ttoo uunniitt nnaammeeppllaattee aanndd iinnssttaallllaattiioonn iinnssttrruuccttiioonnss ffoorr pprrooppeerr cclleeaarraanncceess..
1. Follow the instructions in the maintenance section of the of the Separated Combustion Indoor
Duct Furnace manual for servicing the furnace section of the make-up air unit.
2. Inspect and service the blower section of the system.
3. Inspect and check the operational functions of all safety devices equipped with your unit to
ensure that all devices are performing adequately.