Maximum Cable Lengths
Network topology Maximum cable length
Free topology without repeater 1640 ft [500 m]
Free topology with one repeater 3280 ft [1000 m]
Free topology maximum device-to-device 1640 ft [500 m]
Bus topology single terminated 1640 ft [500 m]
Bus topology double terminated without repeater 8858 ft [2700 m]
Bus topology double terminated with one repeater 17716 ft [5400 m]
Bus topology maximum stub length 9.8 ft [3 m]
Use of the same cable type throughout the entire network is recommended in order to avoid impedance mis-
match.
System Specifications
Up to 64 FT-X1/FTT-10 transceivers are allowed per network segment.
How to install
TR200 LonWorks 4-3