Parameters
Parameter List
Parameter List
Par.
No.
Parameter name: Default value: Range:
Conver-
sion type:
Data
type:
8-01 Control Site Dig. and control word [0] [0 - 2] - 5
8-02 Control Word Source FC Port [1] [0 - 4] - 5
8-03 Control Word Timeout Time 600 s 0.1–18000 1 7
8-04 Control Word Timeout Function Off [0] [0 - 10] - 5
8-05 End-of-timeout Function Hold set-up [0] [0 - 1] - 5
8-06 Reset Control Word Timeout Do not reset [0] [0 - 1] - 5
8-07 Diagnosis Trigger Disable [0] [0 - 3] - 5
8-10 Control Word Profile FC profile [0] [0 - x] - 5
8-50 Coasting Select Logic OR [3] [0 - 3] - 5
8-52 DC Brake Select Logic OR [3] [0 - 3] - 5
8-53 Start Select Logic OR [3] [0 - 3] - 5
8-54 Reversing Select Logic OR [3] [0 - 3] - 5
8-55 Set-up Select Logic OR [3] [0 - 3] - 5
8-56 Preset Reference Select Logic OR [3] [0 - 3] - 5
11-00 Neuron ID 00 00 00 00 00 00 - - 10
11-10 Drive Profile VSD 6010 [0] - - 5
11-15 Lon Warning Word 0 - - 6
11-18 LonWorks Revision [0, 10] - - 9
11-21 Store Data Values Off [0] [0 - 1] - 5
Parameter Group 8-**
8-01 Control Site
Option: Function:
The setting in this parameter overrides the settings in par.8-50
Coasting
Select to par.8-56 Preset Reference Select.
[0] * Digital and ctrl. word Control by using both digital input and control word.
[1] Digital only Control by using digital inputs only.
[2] Control word only Control by using control word only.
8-02 Control Source
Option: Function:
Select the source of the control word: one of two serial interfaces or four
installed options. During initial power-up, the adjustable frequency drive
automatically sets this parameter to
Option A
[3] if it detects a valid serial
communication bus option installed in slot A. If the option is removed,
the adjustable frequency drive detects a change in the configuration, sets
par.8-02
Control Source back to default setting
Adjustable Frequency
Drive Port
, and the adjustable frequency drive then trips. If an option is
installed after initial power-up, the setting of par.8-02
Control Source will
TR200 LonWorks 8-1