In the [Field List:] under the section [par_number], enter the parameter number (in this example 3-41). If an
indexed (array) parameter is accessed, the [subindex] field must be filled in.
130BA454.10
The response may look like this:
Value [0] (1st byte) = 232
Value [1] (2nd byte) = 3
- meaning that the readout value of parameter 3-41 is: 232+(3x256) = 1000
Conversion index of par. 3-41 is: -2(0.01)
Ramp 1 Ramp-up Time = 1000x0.01 =
10 seconds
How to access TR200 parameters
7-4 TR200 LonWorks