Output variables
Variable function Variable name SNVT type Profile
TR200
Par.
Status word nvoStatusword SNVT_state FC VSD 16-03
Drive output [%] nvoOutputPcnt SNVT_lev_percent FC VSD 16-05
Drive output [Hz] nvoOutputHz SNVT_freq_hz FC VSD 16-13
kWh counter nvoDrvEnrg SNVT_elec_kwh_l FC VSD 15-02
DC Link Voltage nvoDCVoltage SNVT_volt FC VSD 16-30
Motor thermal nvoTempMtr SNVT_lev_cont FC VSD 16-18
Inverter Thermal nvoTempInvrtr SNVT_lev_cont FC VSD 16-35
Closed-loop feed-
back
nvoFeedback SNVT_count_inc_f FC VSD 16-52
Fan belt broken nvoBrokenBelt SNVT_switch FC VSD 16-93
Alarm flag nvoAlarm SNVT_switch FC VSD 16-90
Warning flag nvoWarning SNVT_switch FC VSD 16-03
Alarm word nvoAlarmword SNVT_state_64 FC VSD 16-90 +
16-91
Warning word nvoWarningword SNVT_state_64 FC VSD 16-92 +
16-93
Extended status-
word
nvoExtendedStatu-
sword
SNVT_state_64 FC VSD 16-94 +
16-95
Digital inputs nvoDigitInput SNVT_state_64 FC VSD 16-60
Analog Input (53) nvoAnIn1 SNVT_volt/SNVT_amp_mil/
SNVT_lev_percent
FC VSD 16-62
Analog Input (54) nvoAnIn2 SNVT_volt/SNVT_amp_mil/
SNVT_lev_percent
FC VSD 16-64
Analog Input
(X30/11)
nvo101AnIn1 SNVT_volt/SNVT_lev_percent FC VSD 16-75
Analog Input
(X30/12)
nvo101AnIn2 SNVT_volt/SNVT_lev_percent FC VSD 16-76
Analog Input
(X42/1)
nvo109AnIn1 SNVT_volt/SNVT_temp_p/
SNVT_lev_percent
FC VSD 18-30
Analog Input
(X42/3)
nvo109AnIn2 SNVT_volt/SNVT_temp_p/
SNVT_lev_percent
FC VSD 18-31
Analog Input
(X42/5)
nvo109AnIn3 SNVT_volt/SNVT_temp_p/
SNVT_lev_percent
FC VSD 18-32
ECB option status nvoECBstatus SNVT_state FC VSD 31-10
Parameter access
cmd.
nvoParamRes-
ponse
UNVT_param_response FC VSD -
Configuration of the system
TR200 LonWorks 5-3