ECB Option Status
Variable
name:
SNVT
type:
State:
nvoECBStatus SNVT_state Boolean 1 bit x 16
This variable displays the current status of the ECB option.
Bit 0 Test Mode
Bit 1 Drive Mode
Bit 2 Automatic Bypass Mode
Bit 3 Bypass Mode
Bit 4 Reserved
Bit 5 Motor Running from Bypass/Drive
Bit 6 Overload Trip
Bit 7 M2 Contactor Fault
Bit 8 M3 Contactor Fault
Bit 9 External Interlock
Bit 10 Manual Bypass Override
These variables are available only if the
Electronic Control Bypass option
(ECB) has been installed.
Parameter Access Response
Variable name: SNVT type:
nvoParamResponse UNVT_param_response
This output variable is used for the adjustable frequency drive access.
A special UNVT has been defined for this variable.
For more information on parameter access, please refer to the
How to Access TR200 Parameters
section.
Configuration of the system
5-16 TR200 LonWorks