If a value lower than 20 Hz is entered, nciNmlFreq will be set to 20 Hz.
Min Ramp-up Time [s]
Variable
name:
SNVT
type:
Default value: Min value: Max value:
nciRampUpTime SNVT_time_sec 10 s 1 s 3,600 s
This variable configures the Ramp 1 ramp-up time and associates it with par.3-41 Ramp 1 Ramp-up Time.
Min Ramp-down Time [s]
Variable
name:
SNVT
type:
Default value: Min value: Max value:
nciRampDownTime SNVT_time_sec 10 s 1 s 3,600 s
This variable configures the Ramp 1 ramp-down time and compares it with par.3-42 Ramp 1 Ramp-down
Time.
Heartbeat Time [s]
Variable
name:
SNVT
type:
Default value: Min value: Max value:
nciSndHrtBt SNVT_time_sec 0 s 0 s 6,553.4 s
This variable configures a heartbeat timer to send the following variables:
nvoDrvCurnt
nvoDrvSpeed
nvoDrvVolt
nvoDrvPwr
Setting the timer to 0.0 disables the timer.
Heartbeat timers have the purpose of sending out heartbeat signals containing specific data, enabling manage-
ment systems to prove that the node is present on the network and working correctly. Only bound variables will
be transmitted.
Configuration of the system
TR200 LonWorks 5-21