29
18-HD82D1-1B-EN
XR724 INSTALLER’S GUIDE
Non-VS Air
Handler & Electric Heat
Heat Pump Diagram 3: 1 Stage Heat Pump w/GAM5B Model Air Handler
G
W1
Y
R
B/C
W2
One stage
Heat Pump
Y
R
B
Notes:
1. Jumper “W2” to “W3” if three stages of indoor heat
are available
2. “Y” terminal must be connected at indoor unit for
cooling airflow
Sensor Options in the Installer Settings/Sensor Settings menu
Remote Sensor (connect to the RS terminals)
- None
- Replaces internal sensor
- Average with internal sensor
Outdoor Temp Sensor (connect to the ODT terminals)
- None
- Outdoor
Caution: Do not run sensor wires in the same bundle with HVAC
wires. Keep away from high voltage wiring to avoid interference.
Remote Temperature Sensor Connections and Operation:
Aux relay
outputs
RS
C
RS
R
ODT
W1
W2
BK
ODT
NO
C
Y1
NC
Y2
O/B
G
Thermostat Connection
Outdoor
Sensor
Remote
Sensor
O
W3
X2
O
(Note 1)
(Note 2)
Non-VS Air
Handler & Electric Heat
Heat Pump Diagram 4: 2 Stage Heat Pump w/GAM5B Model Air Handler
G
W1
Y I
R
B/C
Y
W 2
Two stage
Heat Pump
Y1
R
B
Notes:
1. Jumper “W2” to “W3” if three stages of indoor
heat are available
2. “Y2” terminal must be connected at indoor unit
for cooling airflow
Sensor Options in the Installer Settings/Sensor Settings menu
Remote Sensor (connect to the RS terminals)
- None
- Replaces internal sensor
- Average with internal sensor
Outdoor Temp Sensor (connect to the ODT terminals)
- None
- Outdoor
Caution: Do not run sensor wires in the same bundle with HVAC
wires. Keep away from high voltage wiring to avoid interference.
Remote Temperature Sensor Connections and Operation:
Aux relay
outputs
RS
C
RS
R
ODT
W1
W2
BK
ODT
NO
C
Y1
NC
Y2
O/B
G
Thermostat Connection
Outdoor
Sensor
Remote
Sensor
O
W3
X2
O
(Note 1)
(Note 2)
2
Y2
Heat Pump Wiring Diagrams