PKGP-SVX010A-EN
Table 6. Temperature vs. resistance
Temperature
Nominal Resistance
(kOhms)
Degrees °F Degrees °C
-20 -28.9 170.1
-15 -26.1 143.5
-10 -23.3 121.4
-5 -20.6 103.0
0 -17.8 87.56
5 -15.0 74.65
10 -12.2 63.80
15 -9.4 54.66
20 -6.7 46.94
25 -3.8 40.40
30 -1.1 34.85
35 1.7 30.18
40° 4.4 26.22
Table 6. Temperature vs. resistance (continued)
Temperature
Nominal Resistance
(kOhms)
Degrees °F Degrees °C
45° 7.2 22.85
50° 10.0 19.96
55° 12.8 17.47
60° 15.6 15.33
65° 18.3 13.4
70° 21.1 11.89
75° 23.9 10.50
80° 26.7 9.297
85° 29.4 8.247
90° 32.2 7.330
95° 35.0 6.528
Installation

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Trane Precedent WSJ180 and is the answer not in the manual?

Trane Precedent WSJ180 Specifications

General IconGeneral
BrandTrane
ModelPrecedent WSJ180
CategoryAir Conditioner
LanguageEnglish

Related product manuals