24 48663967 Rev 1
Contents
Error
codes
Error Description Error Displayed on
Remote
Unit Response Action to be
Taken by user
0x1E Outdoor temperature
sensor error
Error 30: Outdoor
Temperature sensor
error -- Please Contact
Customer Care
Cool mode or Dry
mode:
Unit will run with
Compressor OFF.
Fan mode:
Run IDU as per user
settings.
Contact
Customer Care
-
Remote not in
network range
NETWORK NOT FOUND
Unit operates as per
previous settings.
Remote must be
in network range
-
Connect to network (if
user did factory reset
on the remote)
CONNECT TO NETWORK
Unit operates as per
previous settings
Contact service
technician
-
AC switched OFF
(main power OFF)
SET POINT TEMP +
INFRARED ACTIVATED +
NO NETWORK FOUND
Switch ON main
power/check the
plug
Lock with AC
- Lock not installed
NIGHT LATCH FAILED --
LOCK NOT INSTALLED
Lock is not in
network
-
Night latch not
operating
NIGHT LATCH FAILED --
PLEASE CHECK YOUR
LOCK
Change Battery
of Lock or
Check Lock is
in Network by
doing Home/
Away Operations
- Door Open
NIGHT LATCH FAILED --
DOOR OPEN
Close door
Refer Section 2.3.1 for LED indications