10
PUB. NO. 22-1802-03
Performance
Data
SW7 SW8 0.1 0.3 0.5 0.7 0.9
CFM 745 758 758 761 735
Temp. Rise 52 51 51 51 52
Watts 68 111 153 197 231
CFM 839 864 851 851 822
Temp. Rise 46 45 45 45 47
Watts 87 134 181 224 263
CFM 934 961 943 941 933
Temp. Rise 41 40 41 41 41
Watts 110 164 211 263 310
CFM 1064 1077 1085 1086 1077
Temp. Rise 56 55 55 55 55
Watts 152 205 262 325 379
CFM 1197 1226 1241 1230 1229
Temp. Rise 50 48 48 48 48
Watts 201 271 338 395 462
CFM 1345 1375 1376 1371 1320
Temp. Rise 44 43 43 43 45
Watts 272 348 418 480 517
High OFF
Medium** ON
ON
*UD2C080AFV42A Furnace Heating Airflow (CFM) and Power (watts) vs. External Static Pressure With Filter
Airflow
Setting
Dip Switch Setting External Static Pressure
Low
High
Low
Medium**
ON
ON
Heating
Heating
1st Stage
Heating
2nd
Stage
OFF
OFF
ON ON
OFF
OFF
OFF
SW1 SW2 SW3 SW4 0.1 0.3 0.5 0.7 0.9
CFM 840 862 850 846 824
Watts 87 135 182 223 264
CFM 962 977 974 973 965
Watts 118 167 221 276 320
CFM 1076 1095 1104 1102 1096
Watts 153 212 271 331 390
CFM 1004 1018 1016 1019 1007
Watts 130 183 236 297 343
CFM 1143 1176 1187 1184 1180
Watts 180 267 311 368 436
CFM 1303 1334 1337 1334 1296
Watts 252 326 394 456 502
CFM 1167 1193 1208 1196 1193
Watts 190 255 321 378 443
CFM 1356 1378 1383 1358 1321
Watts 279 355 424 473 518
CFM 1521 1528 1537 1537 1344
Watts 379 545 534 606 556
CFM 1351 1376 1377 1364 1312
Watts 275 357 422 467 515
CFM 1537 1548 1561 1534 1347
Watts 392 468 552 606 538
CFM 1738 1755 1735 1568 1382
Watts 543 652 708 635 563
Notes:
1. * First letter may be "A" or "T".
2. ** Factory setting.
3. Continuous Fan Setting: Heating or cooling airflow is approximately 50% of selected cooling value.
4. For variable speed low speed airflows are approximately 30% of listed values.
5. LOW 350 cfm/ton is recommended for variable speed application for COMFORT & HUMID CLIMATE setting; NORMAL is 400 cfm/ton;
HIGH 450 cfm/ton is for DRY CLIMATE setting.
OFF
OFF
ON
OFF
ON
ON
ON
ON
ON
*UD2C080AFV42A Furnace Cooling Airflow (CFM) and Power (Watts) vs. External Static Pressure With Filter
Dip Switch Setting External Static Pressure
OFF
ONOFFON
ON ON
OFF
OFFONON
ON
OFFOFFON
ON OFF
OFF
ONOFFOFF
OFF
OFFONOFF
ON
OFFOFF
OFF OFF ON
OFFOFF4**
3.5
3
2.5
OFF OFF OFF
Low (350
CFM/Ton)
Normal (400
CFM/ton)
High (450
CFM/ton)
OFF OFF
ON OFF
Airflow
Setting
Normal (400
CFM/ton)
High (450
CFM/ton)
Low (350
CFM/Ton)
Normal (400
CFM/ton)
High (450
CFM/ton)
Cooling
Unit
Outdoor
Low (350
CFM/Ton)
Normal**
(400
High (450
CFM/ton)
Low (350
CFM/Ton)