EasyManua.ls Logo

Trane TVR Pro CO Series - 2.5 E5: Abnormal power supply voltage; 2.5.1 Digital display output; 2.5.2 Description; 2.5.3 Trigger; recover condition

Trane TVR Pro CO Series
118 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
63
2.5 E5: Abnormal power supply voltage
Digital display output
Description
Abnormal power supply voltage.
All units stop running.
Error code is only displayed on the unit with the error.
Trigger / recover condition
Trigger condition: Outdoor unit power supply phase voltage < 170V.
Recover condition: Outdoor unit power supply phase voltage is > 180V.
Reset method: Resume automatically.
Possible causes
Outdoor unit power supply voltage is abnormal or a phase is missing.
Loosened wiring within electric control box.
High voltage circuit error.
Main PCB damaged.

Table of Contents

Related product manuals