76
Procedure
xF6
Electronic expansion valve coil
connection on main PCB is loose
1
Yes
Ensure the sensor is connected properly
No
Electronic expansion valve coil has
malfunctioned
2
Yes
Replace the sensor
No
Replace outdoor main PCB
Notes:
1. Electronic expansion valve coil connections are port CN70, CN71 and CN72 on the main PCB (labeled 18, 19 and 20, respectively, in Figure 5-2.1 in Part 5,
2.1Ports).
2. The normal resistances between EXV coil wiring terminals RED and white / yellow / orange / blue are 40-50. If any of the resistances differ from the value,
the EXV coil has malfunctioned.
Figure 6-2.3: EXV coil wiring terminals