Installation Guide
10 18-HD80D1-3-EN
1200
12"
43%
16"
81%
18" 69% 96% 100% 18" 64% 89% 100% 18" 60% 83% 100% 18" 56% 78% 100%
MANUAL ZONE SIZING
Auto Zone Sizing is the optimal way to determine the amount of air flow into each zone, but this process is not
mandatory. Zone sizes can be set manually using the following guidelines.
EXAMPLE (highlighted below): A 2-zone, 3-ton AC system is configured to move 1200 CFM. Zone 1 has a 12”
zone damper and Zone 2 has a 16” zone damper.
The Normal sizing strategy would set Zone 1 at 43% and Zone 2 at 81%. If Zone 1 had two dampers (6” and 10”)
the zone size % should be added together (11% & 33%) and set to 44%.