Installation
RT-SVX21P-EN 37
Note: Resistance in excess of 2.5 ohms per conductor can
cause deviations in the accuracy of the controls.
Note: Ensure that the wiring between controls and the
unit’s termination point does not exceed two and a
half (2.5) ohms/conductor for the length of the run.
Do not run the electrical wires transporting DC signals
in or around conduit housing high voltage wires.
Route low voltage wiring per illustrations on page 38.
DC Conductors
Table 6. Zone sensor module wiring
Distance from Unit to Control Recommended Wire Size
0 - 150 feet 22 gauge
0 - 45.7 m .33 mm2
151 - 240 feet 20 gauge
46 - 73.1 m .50 mm2
241 -385 feet 18 gauge
73.5 - 117.3 m .75 mm2
386 - 610 feet 16 gauge
117.7 - 185.9 m 1.3 mm2
611 - 970 feet 14 gauge
186.2 - 295.7 m 2.0 mm2
Figure 40. Typical field wiring diagrams for
electromechanical
Figure 41. ReliaTel™ conventional thermostat field
wiring diagrams
Figure 42. ReliaTel™ options module
Figure 43. ReliaTel™ relative humidity sensor
(dehumidification option)