EasyManua.ls Logo

Tridonic DALI basicDIM DGC - Page 28

Default Icon
48 pages
Print Icon
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
Product manual basicDIM DGC | 07-2018 | 1.9 | en
Functions
c
28 / 48
The position and mounting height produce two different detection areas:
Calculating the diameter:
d2 = 2 × tan(0,5 × ) × h
Typical example values of detection area:
Height h (m)
ø d (m)
1.7
3
2.0 3.6
2.3 4.1
2.5 4.5
2.7 4.9
3.0 5.4
3.5 6.3
4.0 7.2
...
Up to 2 m mounting height presence is detected and over 2 m motion is detected._
I NOTICE
The recommended maximum room height is 3 m for office applications and 4 m for corridor applications.
For presence detection, it is vital that arm movements, etc. can be detected. Position the sensor on the ceiling so that the room
user's hands are located in the centre of the detection area and are not concealed by display screens, backs, etc.