EasyManua.ls Logo

Trox Technik FKR-EU - Safety; General Safety Notes; Correct Use

Trox Technik FKR-EU
17 pages
Print Icon
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
Limit switch with fusible link Type 07-2511
Connecting cable length / cross section
1 m / 3 × 0.75 mm
2
Protection level IP 66
Type of contact 1 changeover contact
Switch rating Resistive load 250 V AC / 5 A 250 V DC / 0.4 A 30 V AC/DC / 7 A
Inductive load
cos φ = 0.6
250 V AC / 3 A 250 V DC / 0.03 A 30 V AC/DC / 5 A
Ambient temperature -20 ... +50 °C
The limit switches must be connected in a separately approved casing with an ignition protection according to EN 60079-0.
Dimensions [mm] / Weight [kg]
Nominal size DN 315 355 400 450 500 560 630 710 800
ÆD 314 354 399 449 499 559 629 709 799
A 31 36
ÆD
1
352 392 438 488 538 600 670 750 840
α
45 ° 30 ° 22.5 °
No. of holes 8 12 16
Weight 6.8 7.3 8.5 14.1 16.4 18 21.3 25.7 28.6
Technical data
FKR-EU with fusible link, explosion proof version
Explosion-proof fire damper FKR-EU 7

Other manuals for Trox Technik FKR-EU