8
Preparing for decalcification
• Dissolve 5 AquaGo professional decalcifica-
tion tablets in an acid-resistant bucket in
1.3gallons (5 l) of drinking water. (Duration
approx. 10 min.).
• Open the access door of the AquaGo.
(See “Opening the access door” in the op-
erating instructions for the AquaGo instant
water heater.)
• Switch the AquaGo off at the
POWERswitch(6).
• Open the hot water faucet and wait until
cold water comes.
• Leave the hot water faucet open in order to
depressurize and vent the water system.
• Interrupt the water supply.
• Wait until no more water runs and the water
system is depressurized.
• Attach “Attention Decalcification” signs to all
water withdrawal points (included with the
AquaGo professional decalcification kit).
Connecting the circulation pump
• Remove the water inlet filter. (see Figure 4)
I
II
Easy Drain Lever
Water inlet filter
Water inlet filter
Latch
Figure 4