Hans Turck GmbH & Co.KG • Witzlebenstraße 7 • D-45472 Mülheim an der Ruhr • Tel. +49 208 4952-0 • Fax +49 208 4952-264 • www.turck.com 21 /1105
Note:
The I/O system BL67 does not require
mounting in an extra housing.
It was specially designed for the harsh
industrial environment and for direct
mounting on the machine and in the
process. The system is extremely robust
and protected against dirt, dust and the
most liquids through its high degree of
protection.
However, it is not suited for the following
applications: high pressure jet cleaning,
100% humidity, outdoor installation or
permanent operation in liquids.
General technical data
via opto-coupler
0 to +55 °C (extended temperature range on request)
-25 to +85 °C
5 up to 95 % (inside), level RH-2, no condensation (at 45 °C storage temperature)
according to IEC 60068-2-42/43
10 ppm (rel. humidity < 75 %, no condensation)
1.0 ppm (rel. humidity < 75 %, no condensation)
according to EN 61131
yes
yes
frequency cycles with a change rate of 1 octave/min
20 frequency cycles per coordinate axis
according to EN 61131
according to IEC 68-2-27, 18 shocks, semi-sinusoidal 15 g threshold/11 ms,
each in +/- direction per space coordinate
according to IEC 68-2-29, 1000 shocks, semi-sinusoidal 25 g threshold/6 ms,
each in +/- direction per space coordinate
according to IEC 68-2-31 and free fall according to IEC 68-2-32
1.0 m
0.5 m
7
IP67
according to EN 61131-2/EN 50082-2 (Industrial)
8 kV
4 kV
PC-V0 (Lexan)
CE
UL
CSA
BL67 general
Potential isolation
Ambient temperature
Operating temperature
Storage temperature
Relative humidity
Corrosive gas
–SO
2
–H
2
S
Vibration resistance
10 to 57 Hz,
constant ampitude 0.075 mm, 1 g
57 to 150 Hz,
constant acceleration 1 g
Vibration mode
Vibration duration
Application conditions
Shock resistance
Repetitive shock resistance
Drop and topple
Drop height (weight < 10 kg)
Drop height (weight 10 to 40 kg)
Test cycles
Protection degree
Electromagnetic capability (EMC)
Static electricity according to
EN 61000-4-2
Air discharge (direct)
Relay discharge (indirect)
Housing material
Approvals