1105 Hans Turck GmbH & Co.KG • Witzlebenstraße 7 • D-45472 Mülheim an der Ruhr • Tel. 0208 4952 0 • Fax 0208 4952 264 • www.turck.com
Gateway for BL67 I/O system
Interface for PROFIBUS-DP
BL67-GW-DP
3 decimally coded rotary switches
Degree of protection IP67
LEDs for display of supply voltage,
common alarm and bus errors
Interface between BL67 system and
PROFIBUS-DP
12 Mbps
Two 5-pole reverse-keyed M12 x 1
connectors for fieldbus connection
One 5-pole 7/8" connector for po-
wer connection
Fieldbus
Fieldbus
Power supply
Function principle
BL67 gateways are the head component of
a BL67 station. They are designed to inter-
face the modular fieldbus nodes to the
higher level fieldbus (PROFIBUS-DP,
DeviceNet™, CANopen, Ethernet).
All BL67 electronic modules communicate
via the internal module bus, whose data are
transferred to the fieldbus via the gateway,
so that all I/O modules can be configured
independently of the bus system.
4
13
2
5
1 = 5 VDC
2 = Bus  A
3 = GND
4 = Bus  B
5 = Shield
4
13
2
5
1 = n.c.
2 = Bus  A
3 = n.c.
4 = Bus  B
5 = Shield
3
4
5
2
1
1 = GND
2 = GND
3 = PE
4 = V
i
5 = V
o
Type BL67-GW-DP
Ident-No. 6827184
Supply voltage 24 VDC
Permissible range 18...30 VDC
Nominal current from module bus 650 mA
Max. field current supply 10 A
Max. system current supply 1.5 A
Transmission rate fieldbus 9.6 kbps...12 Mbps
Fieldbus addressing range 1...125
Fieldbus adressing 3 decimally coded rotary switches
Service interface PS/2 socket for I/O-ASSISTANT
Fieldbus connection technology 2 x M12, 5-pole, reverse-keyed
Power connection technology 5-pole male 7/8'' connector
Fieldbus termination external
No. of diagnostics bytes 3
No. of parameter bytes 5
Operating temperature 0...+55 °C
Storage temperature -25...+85 °C
Relative humidity 5 to 95 % (indoor), Level RH-2,
without condensation (storage at 45 °C)
Vibration test according to EN 61131
Shock test according to IEC 68-2-27
Topple and fall according to IEC 68-2-31
and free fall according to IEC 68-2-32
Electromagnetic compatibility according to EN 61131-2
Degree of protection IP67
General technical data see page 21